Digital combustible detector for oxygen, or toxic gases
The OLCT 10N is a digital combustible gas detector designed for to detect combustible, toxic gases or oxygen.
Intended for use in combination with the MX 43 controller, the OLCT 10N provides a fast and accurate response. Up to 32 detectors can be connected on the same digital line or distributed on 8 lines.
All transmitter information is received by the controller in less than 1 second.
Non-intrusive operator interface requires only a simple magnetic wand and allows one man calibration without opening the enclosure.
Detection of combustible gases, toxic gases or oxygen
Digital technology
Non-intrusive calibration
Cost savings on wiring installation
Range |
CH4, C3H8, C4H10, H2 0-100 % LIE (-20°C à + 55°C) O2 (> 2 years) 0-30 % vol (-20°C à + 50°C) O2 (5 years) 0-30 % vol (-40°C à + 50°C) CO 0-300 ppm / 0-1000 ppm (-20°C à + 50°C) H2S 0-30 ppm / 0-100 ppm (-20°C à + 50°C) NO 0-100 ppm / 0-300 ppm (-20°C à + 50°C) NO2 0-10 ppm / 0-30 ppm (-20°C à + 50°C) NH3 0-100 ppm / 0-1000 ppm (-20°C à + 40°C) CO2 0-5000ppm / 0-5% vol / 0-100% vol (-40 à + 50°C) |
Output |
RS485 Modbus, proprietary protocol |
Power supply |
12-30 Vcc |
Consumption |
Electrochemical sensor: 2.5 mA in normal operation @ 24 Vdc Catalytic sensor : 50 mA in normal operation @ 24 Vdc CO2 Infrared sensor: 20mA in normal operation @24Vdc |
Calibration |
Non-intrusive |
Cable inlet |
2 PE M16, diamètre 4 à 8 mm |
Cable inlet |
2 x M16 cable entries, outer diameter 4 to 8 mm Up to 32 detectors at 1000 m with a 0.9 mm² (AWG 18) core size cable |
Dimensions (LxHxW) |
118x110x60 mm |
Materials |
ABS, UV and shocks resistant |
Ingress protection |
IP65 |