Data sheet

EE451

E+E sensors EE451 are used for temperature measurement in heating, ventilation and air conditioning systems enabling weather-dependent temperature regulation.

In addition to active outputs 0-10 V or 4-20 mA various types of sensing elements such as Pt1000, NTC10k or Ni1000 are available for passive temperature measurement.

The innovative enclosure concept (IP65) with a mounting bracket allows for easy installation and unbiased detection of ambient temperature.

  • External mounting holes

  • Bayonet screws

  • Mounting bracket

MEASURING RANGE PASSIVE OUTPUT

-40…70 °C (-40...158 °F)

T-SENSOR CONNECTION

two-wire

MEASURING RANGE ACTIVE OUTPUT

-40…70 °C (-40...158 °F)

ACCURACY

±0.3 °C (±0.54 °F)

PROTECTION CLASS

IP65 / NEMA 4

OUTPUTS

0-10 V or 4-20 mA

POWER

24 V AC/DC